Repository navigation
Open
Description
Purpose
CI and simulator certification for P6A–P6E are complete. This issue tracks physical-device field acceptance, which must not be inferred from simulator success.
Validated engineering baseline: baseline/ux-p6e-validated -> de8ba6e32f1e21effffc967f9f04b82d457f8451.
Field test plan
- Use at least two authorized, reachable IEC 61850 IEDs; maintain two simultaneous Browser sessions and confirm independent endpoint, model, association, report/control service and Global Data identity during switching.
- Exercise Open SCL and Discovery ingress on the same device; compare canonical LD/LN/DO/DA, DataSet directories/order, RCB references and exported SCL with an independently captured aplikasi pembanding reference.
- With the known AA1E1F06R4 fixture, verify 2 static DataSets (Analog=22, Digital=36), 58 descriptors, and 46 exact runtime rows, as applicable to the actual device firmware/configuration; record discrepancies instead of forcing counts.
- Verify Discovery -> Static Dataset -> static report-only matches Open SCL -> Static Dataset; inspect BRCB/URCB selection, GI, ConfRev, report values and no cyclic MMS polling fallback.
- Verify a guarded Control operation only on a safe/authorized test point with explicit operator confirmation and positive/negative CommandTermination evidence as provided by the device. Do not perform live process-impacting controls without site approval.
- Verify dynamic DataSet create/read-back/owned-only delete and authored RCB DatSet/TrgOps/OptFlds on an authorized test IED; restore canonical binding and clean up.
- Capture live passive MMS TCP/102 via explicit NIC selection and compare decoded Read/Write/Report/Control evidence with a simultaneously recorded PCAP. Confirm no active association/packet injection by Sniffer.
- Verify disconnect/reconnect, application shutdown, session cleanup and multiple IEDs under realistic load; record Windows Npcap permission/driver requirements.
- Attach sanitized logs/PCAP/SCL, platform/version, IED firmware, exact build SHA and observed deviations.
Boundaries
P6D currently claims IPv4 TCP/102 and classic Ethernet PCAP; IPv6, fragmented IPv4 defragmentation, PCAPNG and exhaustive semantic decode are not certified. Do not silently extend the claim.
Field acceptance remains OPEN until the required physical-device evidence is attached and reviewed. No release/parity claim should imply it already passed.
Metadata
Metadata
Assignees
Labels
No labels
Activity
masarray commentedon Sep 26, 2026
P6 field-trial handoff — tested Windows RC (26 September 2026)
Build provenance:
baseline/ux-p6e-validated/de8ba6e32f1e21effffc967f9f04b82d457f8451; the same SHA is currentmainat this checkpoint. Post-merge CI 11/11 SUCCESS, including IED Simulator Qt, C++ CI, Security/Evidence, and Windows/Linux Release Hardening.Download: GitHub Actions artifact #10903578577 (
arstack-iec61850-workbench-windows-rc, expires 10 October 2026). The artifact ZIP contains:ARStack-IEC61850-Workbench-portable-win64.zip: extract all into a user-writable folder, runarstack_ied_simulator.exe; no admin install needed.ARStack-IEC61850-Workbench-Setup-win64.exe: NSIS install; requests administrator privileges and defaults to Program Files.df9bfa966d55dc380ebd8d030435961c117bca3a021b44d872839e748ffe251e.Suggested field-trial order (record actual outcomes, do not infer physical-device success from CI):
Submit findings in #124 with build SHA, Windows version, portable/installer choice, IED model/firmware, sanitized SCL/PCAP/logs/screenshots, expected vs observed behavior, and exact reproduction steps. Scope limitations: no IPv6, fragmented IPv4 defragmentation, PCAPNG or exhaustive MMS semantic decoding claim; physical IED acceptance remains OPEN until actual evidence is reviewed.
This is a field-trial RC, not a declaration of full physical-device or IEDScout parity.