Physical lab failure reproduced (sanitized summary; do not commit operator PCAP)
From a 4I+4V / 4000 fps IEC 61850 Sampled Values lab publisher, the raw 64-byte ASDU contains eight [INT32 instMag.i + quality] pairs. Example setpoints: 1.000 A corresponds to 1000 raw counts; 57.740 V corresponds to 5774 raw counts. The current SCL-free raw 4I4V candidate maps the channels, waveform and angles correctly, but the Metering panel treats ~999 raw counts as 999 A and ~5774 raw counts as 5.77 kV, and computes false MW/Mvar/MVA. The actual lab profile expresses currents at 1/1000 A/count, voltages at 1/100 V/count. No subscriber or switch is needed for reproduction; synthetic owned golden frames suffice.
Root-cause starting point
RawProcessBusAnalyzer.SvStreamState.ObserveSamples() stores big-endian INT32 decoded counts without an explicit engineering scale authority, yet CreateChannelValue() labels numbers A and V; MainWindowViewModel.ComputeThreePhasePower() multiplies these unqualified values to calculate W/var/VA. SCL mapping currently provides channel order but not necessarily calibration. Do not fix by silently dividing all streams by hard-coded factors or keying vendor/svID names.
Required robust fix
- Establish a single per-stream, versioned scale/source authority: raw counts (unknown physical unit), explicitly selected 9-2LE/61869-9 compatible nominal profile where justified, or validated engineering context. Keep the selected stream's waveform/RMS/phasor/metering coherent.
- Without confirmed scaling, label magnitudes as raw counts and show P/Q/S/PF as unavailable (not fabricated MW/Mvar). Make missing scale and how to resolve it obvious to novice users.
- Provide an easy no-SCL path to select/verify a known 4I+4V 9-2LE nominal profile (1 mA/count current, 10 mV/count voltage) with clearly marked evidence/provenance; never silently apply it to arbitrary publisher layouts.
- Changing scale must atomically invalidate dependent derived views for the selected stream, without resetting capture ownership or mixing other stream identities.
- Deterministic regression: 1 A and 57.74 V show near those figures and no bogus MW, preserving +30° dynamic phase changes; negative tests unknown scaling, malformed layout, second independent diagnostic stream, zero/neutral channels, switching selected stream, and no regressions in raw waveform shape/timing.
- Follow repository AGENTS.md & src/AGENTS.md: bounded hot path, no synthetic waveform, no uncertain physical unit claims.
Dependencies
Source ARStack Studio flash-build mismatch is independently addressed in arstack61850 PR #189. This issue is for DigSubAnalyzer's receive-only interpretation, not ARStack firmware and not a request to embed a publisher in the analyzer.